UT-101/102 | UNIVERSAL PROCESS CONTROLLER
 
   Datasheet | Manual
 
Available Size : 96 x 96 , 96 x 48 (H) ,48 x 96 (v) External Box : Ex. Flameproof / M S or S S Box
 
Feature:- INPUT (For all channel)
►  Microprocessor based powerful & highly reliable controller.
►  Universal Input T/C, RTD, linear input selection.
► Potential Free Relay contact output up to 1 / 2 / 3 / 4 Nos.
►  0.1% Accuracy of FSD.
►  Isolated 0/4-20 mA process value retransmission output.
►  All Configurations and Calibration from front panel keypad.
►  High speed communicative serial (RS 232/485) interface.
►  Transmitter loop power supply with current limit as standard.
►  Power supply : 230V/110V AC or 24V/12V DC.
►  Optional GSM mobile connectivity.
►  Fully Password Protected Operation.
Type Range Code
J -0050 to 0750 ˚C JTC
K -0050 to 1200 ˚C KTC
R  0000 to 1750 ˚C RTC
S  0000 to 1750 ˚C STC
T  0000 to 0400 ˚C TTC
E -0050 to 0500 ˚C ETC
PT-100 -0050 to 0400 ˚C PT
CU 53 -0050 to 0250 ˚C PCU
LINEAR -1999 to 9999 LNI
 
 
Computer Software (SCADA) Available for On line Process Viewing, Controlling and Data logging.
 
Technical Specification:-
Input Input Type T/C K, J, R, S, E, N, T
RTD Pt100, Cu53 ( 2 wire & 3 wire )
Currant 0 ~ 20mA DC, 4~20mA DC
Voltage 0-5V/1-5V, 0.5-2.5V/0- 10 V DC
Special on demand 0-75/200 mV & 0-1/10V/100/300/V DC
0-75/200 mV 0-100/300V DC
Resistence 0-500Ω , 0-1/5/10/100 K Ω
Transmitter power supply 24 V DC @ 30 mA max, isolated from I/p & O/P.
Cold junction comp. & Sensor break ind. Software base Automatic.
Range limits As per input range table
Accuracy +/- 0.1 % of span for linear & RTD, +/-0.25 % for T/C
Input impedance >330 KΩ for Voltage ,mV, and T/C , 100Ω for current
Indication Indication PV & SV for UT102 & PV for Ut101- 0.56” 4 digit 7 segment display
Control Mode Status indication LEDs for Relay status & Communication
Output On Off control Relay / SSR
Dead Band control High and Low Set point for level application
Relay Output • NO - C - NC Contacts , 5A@240 V AC Resistive 
• 1 / 2 / 3 / 4 Relays / SSR output
SSR Output 24VDC @ 20 mA ,12VDC @ 20 mA
Retransmission Current & Voltage O/P 0~20/ 4~20 mA, 0~5V, 0~10V, 1~5V DC, fully 3 port isolated 1.5KV
Communication Protocol & method Modbus RTU RS-485/RS-232 communication
Communication Programmable parameter & Connectable number Baud rate, Parity, Node address, stop bit & 0-256 unit
Wireless communication GSM/GPRS base mobile (sms) communication
Setpoint / Hysteresis / High scale Low scale Full range as per input selection.
Programmable Relay logic • F.S. high & low alarm
• Dead band alarm
Display resolution -1999 to 9999 fully configurable for linear input
Programming of parameters Through 4 tactile keys
(A) Dimensions  (A) 96(H) x 96(W) x 100(D) 
(B) Panel cutout  (B) 92 x 92 
(C) Mounting (C) panel mounted
Other (A) Supply voltage  (A) 110/230 V AC, 50/60 Hz 
(B) Power consumption (B) 4 watt maximum
Operating ambient temperature and humidity •  0~50 °C 
•  Below 90%, non condensing
 
 
Datasheet | Manual