Home | Support | Inquiry | Career | Contact UsDealers                       
Home > Product >FLP Instruments> FLP Proof Multi Channel Indicator
 
DATASHEET | UT-304/308-F1 | FLP MULTI POINT PROCESS INDICATOR
 
   Datasheet | Manual
 
 
Feature:- INPUT(For All Chanel)
► Flame proof low cost and compact size controller.
► µP Based Power, full & highly reliable controller.
► I, IIA,IIB, IP 65 as per IS 2148/1981,certified by C.M.R.I.
► 4/8 nos. Universal Input T/C, RTD, Linear input selection.
► 0.1% Accuracy of FSD.
► All Configurations and calibration from front panel keypad.
► Highly communicative serial interface facility (RS 232/485).
► Transmitter loop power supply with current limit as standard.
► Power supply :230V/110V AC or 24V/12V DC.
► Fully Password Protected Operation.
Type Range
J -50 to 750 ˚C
K -50 to 1200 ˚C
R 0 to 1750 ˚C
S 0 to 1750 ˚C
T 0 to 400 ˚C
E -50 to 500 ˚C
PT-100 -50 to 400 ˚C
CU 53 -50 to 250 ˚C
LINEAR -1999 to 9999
SPECIAL -1999 to 9999
 
Computer Software (SCADA) Available for On line Process Viewing, Controlling and Data Logging.
 
Technical Specification:-
Flame Proof Gas group I IIA IIB as per IS 2148/1981
Enclose certification Enclosure is certified by C.M.R.I., Dhanbad
Display glass Clear glass thognet type A as per IS 2206
Degree protection IP 65 as per IS 2147
Material of constructions Aluminum alloy
Cable entry UT-304-F1=5 x 3/4 “ET    UT-308-F1=12 x 3/4 “ET
External keys 4 nos push buttons
Input

Input Type

For Input 4 or 8

T/C K, J, R, S, E, N, T
RTD Pt-100, Cu53 ( 2wire & 3 wire)
Current 0 ~ 20mA DC , 4~20mA DC
Voltage 0-5V/1-5V, 0.5 -2.5V/0- 10 V DC
Special
on demand
0-75/200 mV & 0-1/10V/100/300 V DC 0-75/200 mV 0-100/300V DC
Resistence 0-500 R , 0-1/5/10 K, 1M
Transmitter power supply 24 V DC @ 30 mA max, Isolated from I/P & O/P
Cold junction comp. & Sensor break ind. Software base Automatic
Range limits As per input range Table
Accuracy +/- 0.1 % of span for linear & RTD, +/- 0.25 % for T/C
Input impedance >330 K for Voltage ,mV and T/C, 100 R for current
Indication Indication 4 digit process value 7 segment display
Status indication LEDs for High and Low alarm status & Communication
Alarm modes High and low
Communication Communication Protocol & mathod Modbus RTU RS- 485/RS- 232 communication
Programmable parameter & Connectable number Baud rate, Parity, Node address, Stop bit & 0-256 unit
Programmable
Parameters
Setpoint / Hysteresis / High scale / Low scale Full range as per input selection
Alarm logic F.S. High & Low alarm
Programming of parameters Through 4 tactile keys
Other (A) Supply voltage (B) Power consumption (A) 110/230 V AC, 50/60 Hz (B) 9 watts maximum
Operating Amb. Temperature and Humidity Temp : 0~50 °C and Humidity :Below 90%, non condensing
 
 