Home | Support | Inquiry | Career | Contact UsDealers                       
Home > Product >Flow Indicator Totalizer > Flow Rate Indicator
 
DATASHEET | UT-1201 | FLOW RATE INDICATOR / TOTALISER
 
   Datasheet | Manual
 
Available size : 96x96-LCD,96x96-LED,96x48 External Box : Ex. Flameproof / M S or S S Box
 
                    Flow Indicator Totaliser UT-1201 is compact and easy to use, designed for monitoring the continuous flow rate and total flow. The flow rate along with engineering units is displayed on the upper line of LCD/LED display and the totalised flow is displayed on 8/10 digits on the second line. The microcontroller based design makes it more flexible and powerful compared to conventional flow totaliser. The unit is suitable for use with any flow transmitter giving pulse or analog current output. The display has floating decimal point position, which is programmable from the front panel. The unit has inbuilt relay outputs for Flow rate and Totaliser of alarm or control application.

                     Unitech flow totaliser are available for liquid and gas duties and are available as field/ wall mounting or alternatively in an explosion proof housing to the latest international standards and will work with orifice any type of flowmeter. Options include pulse and/or 4-20mA retransmission or communications outputs to printers or SCADA control systems.
 
Feature:- Applications:-
► Accepts Universal inputs – 4-20 mA or 0-10 V or pulse (3 & 2 wire)
     input type.
► Non-volatile memory to retain totaliser flow, no need to battery      change.
► Potential Free Relay contact output 2 x Flow and 2 x Totaliser.
► Liner or Square root input selections with 0.1% Accuracy.
► Isolated 0/4-20mA retransmission output proportional to standard      own rate.
► Field operated user friendly menu for device configurations &
     calibration.
► 8/10 digit Flow Totaliser with password protected resetting.
► Fully password protection for Tamper free operation.
► Isolated Highly communicative serial interface facility
      (RS 232/485).
► 24 V loop power supply for Flow Transmitter.
► Optional GSM mobile connectivity for wireless remote reading      purpose.
► Flow Metering computer software Available.
► Weather proof or flame proof housing.
► Remote Pipeline Measurement
► Chemical Batching in
► Hazardous Areas
► Tank Farm Level Monitoring
► Brewery Batch Controllers
► Oil Storage Depot Deliveries
► Effluent Discharge Metering
► Storage Tank Steam Trace Heating
► Crude Oil/Water Cut Measu.
► High Pressure Gas Transfer
► Terminal Automation Software
► LPG Distribution
► Bulk Solvent Delivery
 
Suitable for Orifice , DPT/ Pitot tube /Turbine
venturi and vortex flow meters
Flow managements Computer software available.
 
Technical Specification:-
Input

Input Type


Transmitter power supply
Currant 0 ~ 20mA DC , 4~20mA DC
Voltage 0-5V/1-5V, 0.5 -2.5V/0- 10V DC
Pulse PNP / NPN / 2 wire namur type
24 V DC @ 30 mA max, Isolated from I/P & O/P
Range limits 0.1 to 99999 Programable with decimal point selection
Accuracy +/- 0.1 % of span
Input impedance >330 K for Voltage & 100 R for Current
Input mode Linear or Square root
Indication Indication LED TYPE: 5 digit Flow rate & 8 digit Totaliser-7 segment led display
LCD TYPE: 5 digit Flow rate & 10 digit Totaliser-16x2 line back lite
Status indication LEDs for Relay status & Communication
Alarm modes Very Low / Low / High / very High
Control Mode On Off controls Relay
Output Relay Output • NO - C - NC Contacts , 5A@240V AC Resistive
• 1 / 2 / 3 / 4 Relays / SSR Output
Retransmission Current & Voltage outputs 0~20/ 4~20 mA, 0~5V, 0~10V, 1~5V DC, fully 3 port isolated
Communication Programable parameter & Connectable number Baud rate , Parity , Node address , Stop bit & 0-256 unit
Wireless communication GSM/GPRS base mobile(sms) Communication
Programmable
Parameters
Setpoint / Hysteresis / High scale / Low scale Full range as per input selection
Relay logic F.S. High & Low potential free contact
Display resolution 0 to 99999 fully configurable for linear input
Programming of parameters Through 4 tactile keys
Other (A) Dimensions (B) Panel cutout (C) Mounting (A) 96(H) x 96(W) x 100(D) (B) 92 x 92 (C) panel mounted
(A) Supply voltage (B) Power consumption (A) 110/230 V AC, 50/60 Hz (B) 4 watts maximum
Operating ambient temperature and humidity • 0~50 °C        • Below 90%, non condensing
Flame Proof Gas group I IIA IIB as per IS 2148/1981
Enclose certification Enclosure is certified by C.M.R.I., Dhanbad
Display glass Clear glass thognet type A as per IS 2206
Degree protection IP 65 as per IS 2147
Material of constructions Aluminum alloy
Cable entry 3 x 3/4 “ ET
External keys 4 nos push buttons
 
 
Datasheet | Manual