Home | Support | Inquiry | Career | Contact UsDealers                       
Home > Product > FLP Instruments > Flame Proof Universal Indicator
 
UT-101/102-FC1/FC2/FC3 | FLP PROCESS CONTROLLER
 
   Datasheet | Manual
 
 
Feature:- INPUT

►  Flame proof low cost and compact size controller.
►  µP Based Power, full & highly reliable controller.
►  I, IIA,IIB, IP 65 as per IS 2148/1981,certified by C.M.R.I.
►  Universal Input T/C, RTD, Linear input selection.
►  Potential Free Relay contact output upto ½/3/4 .
► 0.1% Accuracy of FSD.
►  Isolated 0/4-20mA process value retransmission output.
►  All Configurations and calibration from front panel keypad.
►  Highly communicative serial interface facility (RS 232/485).
►  Transmitter loop power supply with current limit as standard.
►  Power supply :230V/110V AC or 24V/12V DC
►  Optional GSM mobile connectivity.
►  Fully Password Protected Operation.

Type Range
J -0050 to 0750 ˚C
K -0050 to 1200 ˚C
R  0000 to 1750 ˚C
S  0000 to 1750 ˚C
T  0000 to 0400 ˚C
E -0050 to 0500 ˚C
PT-100 -0050 to 0400 ˚C
CU 53 -0050 to 0250 ˚C
LINEAR -1999 to 9999
SPECIAL -1999 to 9999
   
 
Computer Software (SCADA) Available for On line Process Viewing, Controlling and Data logging.
 
Technical Specification:-
Flame Proof Gas group I IIA IIB as per IS 2148/1981
Enclose certification Enclosure is certified by C.M.R.I., Dhanbad
Display glass Clear glass thognet type A as per IS 2206
Degree protection IP 65 as per IS 2147
Material of constructions Aluminum alloy
Cable entry 3/ 5/ 7 x 3/4 “ET
Input Input Type T/C K, J, R, S, E, N, T
RTD Pt100, Cu53 ( 2 wire & 3 wire )
Currant 0 ~ 20mA DC, 4~20mA DC
Voltage 0-5V/1-5V, 0.5-2.5V/0- 10 V DC
Special on demand 0-75/200 mV & 0-1/10V/100/300/V DC
0-75/200 mV 0-100/300V DC
Resistence 0-500 R , 0-1/5/10 K, 1M
Transmitter power supply 24 V DC @ 30 mA max, isolated from I/p & O/P
Cold junction comp. & Sensor break ind. Software base Automatic
Range limits As per input range table
Accuracy +/- 0.1 % of span for linear & RTD, +/-0.25 % for T/C
Input impedance >330 K for Voltage ,mV, and T/C, 100 R for current
Indication Indication PV & SV for UT102 & PV for UT101- 4 digit 7 segment display
Status indication LEDs for Relay status & Communication
Alarm modes Very Low/Low/High/very High
Control Mode On Off control Relay / SSR
Dead Band control High and Low Set point for level application
Output Relay Output • NO - C - NC Contacts , 5A@240 V AC Resistive 
• 1 / 2 / 3 / 4 Relays / SSR output
SSR Output 24VDC @ 20 mA ,12VDC @ 20 mA
Retransmission Current & Voltage O/P 0~20/ 4~20 mA, 0~5V, 0~10V, 1~5V DC, fully 3 port isolated 1.5KV
Communication Communication Protocol & method Modbus RTU RS-485/RS-232 communication
Programmable parameter & Connectable number Baud rate, Parity, Node address, stop bit & 0-256 unit
Wireless communication GSM/GPRS base mobile (sms) communication
   
Programmable Setpoint / Hysteresis / High scale Low scale Full range as per input selection.
Relay logic • Heat
• F.S. high & low alarm
• Dead band alarm
•Cool
Display resolution -1999 to 9999 fully configurable for linear input
Programming of parameters Through 4 tactile keys
Other Dimensions & Mounting As per box selection & wall/structure 2/4 holes
(A) Supply voltage  (A) 110/230 V AC, 50/60 Hz 
(B) Power consumption (B) 4 watt maximum
Operating ambient temperature and humidity •  0~50 °C 
•  Below 90%, non condensing
 
 